Adjustable Over/Under Voltage & Overcurrent Protector (AVP)
Product Details
Product Overview
-
Fully Adjustable Parameters
All protection parameters including voltage, current, and delay times can be precisely set via front panel buttons.
-
Digital Display
Bright digital tube displays real-time voltage, current values, and operational status for clear monitoring.
-
Self-Recovery Function
Automatically or manually restores power after fault elimination, significantly reducing maintenance costs.
-
Multi-Protection
Integrates overvoltage, undervoltage, overcurrent, and rapid power-failure protection for comprehensive equipment safety.
-
DIN-Rail Mounting
Standard 35mm DIN-rail installation for easy integration into various distribution boxes and control cabinets.
-
B2B Bulk Supply
Focused on large-scale projects and wholesale orders with competitive pricing, stable supply, and professional technical support.
|
Rated supply voltage |
AC220V |
Operation voltage range |
AC80V~400V |
|
Rated frequency |
50/60Hz |
Current (>A) setting range |
1-40/63A |
|
Overvoltage(>U)setting Range |
230-300V |
Under voltage (<U) setting range |
210-140V |
|
Rated Current |
40/63A |
Voltage measurement accuracy |
2%(Not exceeding 2%of the overall range) |
|
ResetStartDelay |
1~600S |
Output contact |
1NO |
|
Rated Insulation Voltage |
400V |
Mechanical life |
106 |
|
Electrical life |
105 |
Pollution Degree |
3 |
|
Protection Degree |
IP20 |
Operatintg temperature |
-50℃ ~55℃ |
|
Altitude |
≤ 2000m |
Storage temperature |
-30℃ ~70℃ |
|
Humidity |
≤ 50% at 40℃ (without condensation) |
>U and<U trip delay |
0.5s |
|
Technical Parameter |
Setting range |
Step |
Factory Setting |
|
Power on delay time |
1-300s |
1s |
5s |
|
Overvoltage protection value |
230V-300V |
1V |
280V |
|
Undervoltage protection value |
210V-140V |
1V |
160V |
|
Voltage protection action time |
0.1-30s |
0.1s |
1s |
|
Overcurrent protection value |
1-40/63A/OFF |
0.1A |
40/63A |
|
Overcurrent protection action time |
0.1-30s |
0.1s |
1s |
|
Continuous overcurrent protection frequency |
A01~A20/OFF |
A01 |
OFF |
|
Recovery delay time |
1-600s |
1s |
5s |
|
Current regulations |
15A |
25A |
32A |
40A |
50A |
63A |
|
Rated working current (In,A) |
15 |
25 |
32 |
40 |
50 |
63 |
|
Maximum operating current Imax (A,within 10 minutes) |
25 |
30 |
40 |
50 |
60 |
80 |
|
Maximum load power (KW) |
3.6 |
5.5 |
7 |
8.8 |
11 |
13.9 |
|
No. |
Option code |
Option |
max |
min |
Default |
Step |
Unit |
Description |
|
P1 |
Pt |
Power-on delay |
999 |
1 |
5 |
1/10 |
S |
|
|
P2 |
rt |
Recovery delay |
999 |
1 |
30 |
1/10 |
S |
|
|
P3 |
oU |
Overvoltage |
300 |
130 |
270 |
1/10 |
V |
Close overvoltage if greater than 300 |
|
P4 |
oUr |
Overvoltage recovery value |
295 |
125 |
265 |
1/10 |
V |
Skip this setting when overvoltage is turned off |
|
P5 |
uU |
Undervoltage |
210 |
80 |
170 |
1/10 |
V |
Close undervoltage if below 80 |
|
P6 |
uUr |
Undervoltage recovery value |
215 |
85 |
175 |
1/10 |
V |
Skip this setting when undervoltage is turned off |
|
P7 |
Utt |
Overvoltage action delay |
10.0 |
0.1 |
0.5 |
0.1/1.0 |
S |
|
|
P8 |
UAd |
Voltage correction |
+10% |
-10% |
0 |
0.5% |
V |
Long press setting is not recommended |
|
P9 |
oC |
Overcurrent |
63.0 |
1.0 |
63.0 |
0.1/1.0 |
A |
Close overcurrent if greater than 63.0 |
|
P10 |
Ctt |
Overflow as delay |
10.0 |
0.1 |
1.0 |
0.1/1.0 |
S |
|
|
P11 |
CC |
Continuous overcurrent counting |
20 |
0 |
0 |
1 |
Times |
0:Turn off counting |
|
P12 |
CAd |
Current correction |
+10% |
-10% |
0 |
0.5% |
A |
Long press setting is not recommended |
|
P13 |
FAd |
Frequency correction |
+2.5% |
-2.5% |
0 |
0.1% |
Hz |
Modifying this value will affect the accuracy of the timer |
|
P14 |
FPd |
Rapid power failure protection |
on |
off |
on |
|
MS |
|
|
P15 |
dS |
Display mode |
3 |
1 |
1 |
1 |
|
1:Standards |
|
2:Manual switch |
||||||||
|
3:Automatic switch |
||||||||
|
P16 |
Ar |
Automatic reset |
on |
off |
on |
|
|
on:Self-recovery |
|
off:Manual recovery |
||||||||
|
P17 |
Act |
Action/knife mode |
on |
off |
on |
|
|
on:Protector working properly |
|
off:knife mode |
||||||||
|
P18 |
EC |
Energy saving mode |
on |
off |
off |
|
|
on:Open |
|
off:Close |
||||||||
|
P19 |
Loc |
Setup lock password |
999 |
000 |
112 |
1/10 |
|
When this value is not 112,you can only view the parameter and cannot set it |

Product Specification & Installation
Wiring and shape dimensions
Product display