Leave Your Message
Adjustable Over/Under Voltage & Overcurrent Protector (AVP)
AVP

Adjustable Over/Under Voltage & Overcurrent Protector (AVP)

Adjustable Over/Under Voltage & Overcurrent Protector (AVP) – B2B Wholesale | 220V AC, 40/63A, Digital Display, Self-Recovery Multi-Protection for Bulk Residential & Commercial Distribution Projects

    Product Details

    Product Overview

    Our Adjustable Voltage & Current Protector (AVP) is a DIN-rail mounted, digital multi-protection device tailored for B2B bulk applications in residential, commercial, and light industrial distribution systems. Combining overvoltage, undervoltage, overcurrent, and rapid power-failure protection with fully customizable parameters, this self-recovery protector safeguards electrical equipment while enabling seamless integration into standard distribution boxes. It is designed for wholesale orders and large-scale engineering projects, delivering consistent, compliant performance across diverse installations.

    Rated supply voltage

    AC220V

    Operation voltage range

    AC80V~400V
    (single-phase)

    Rated frequency

    50/60Hz

    Current (>A) setting range

    1-40/63A

    Overvoltage(>U)setting Range

    230-300V

    Under voltage (<U) setting range

    210-140V

    Rated Current

    40/63A
    (subject to prodect label)

    Voltage measurement accuracy

    2%(Not exceeding 2%of the overall range)

    ResetStartDelay

    1~600S

    Output contact

    1NO

    Rated Insulation Voltage

    400V

    Mechanical life

    106

    Electrical life

    105

    Pollution Degree

    3

    Protection Degree

    IP20

    Operatintg temperature

    -50℃ ~55℃

    Altitude

    ≤ 2000m

    Storage temperature

    -30℃ ~70℃

    Humidity

    ≤ 50% at 40℃ (without condensation)

    >U and<U trip delay

    0.5s

    Technical Parameter

    Setting range

    Step

    Factory Setting

    Power on delay time

    1-300s

    1s

    5s

    Overvoltage protection value

    230V-300V

    1V

    280V

    Undervoltage protection value

    210V-140V

    1V

    160V

    Voltage protection action time

    0.1-30s

    0.1s

    1s

    Overcurrent protection value

    1-40/63A/OFF

    0.1A

    40/63A

    Overcurrent protection action time

    0.1-30s

    0.1s

    1s

    Continuous overcurrent protection frequency

    A01~A20/OFF

    A01

     OFF

    Recovery delay time

    1-600s

    1s

     5s


    Current regulations

    15A

    25A

    32A

    40A

    50A

    63A

    Rated working current (In,A)

    15

    25

    32

    40

    50

    63

    Maximum operating current Imax (A,within 10 minutes)

    25

    30

    40

    50

    60

    80

    Maximum load power (KW)

    3.6

    5.5

    7

    8.8

    11

    13.9

    No.

    Option code

    Option

    max

    min

    Default

    Step

    Unit

    Description

    P1

    Pt

    Power-on delay

    999

    1

    5

    1/10

    S

     

    P2

    rt

    Recovery delay

    999

    1

    30

    1/10

    S

     

    P3

    oU

    Overvoltage

    300

    130

    270

    1/10

    V

    Close overvoltage if greater than 300

    P4

    oUr

    Overvoltage recovery value

    295

    125

    265

    1/10

    V

    Skip this setting when overvoltage is turned off

    P5

    uU

    Undervoltage

    210

    80

    170

    1/10

    V

    Close undervoltage if below 80

    P6

    uUr

    Undervoltage recovery value

    215

    85

    175

    1/10

    V

    Skip this setting when undervoltage is turned off

    P7

    Utt

    Overvoltage action delay

    10.0

    0.1

    0.5

    0.1/1.0

    S

     

    P8

    UAd

    Voltage correction

    +10%

    -10%

    0

    0.5%

    V

    Long press setting is not recommended

    P9

    oC

    Overcurrent

    63.0

    1.0

    63.0

    0.1/1.0

    A

    Close overcurrent if greater than 63.0

    P10

    Ctt

    Overflow as delay

    10.0

    0.1

    1.0

    0.1/1.0

    S

     

    P11

    CC

    Continuous overcurrent counting

    20

    0

    0

    1

    Times

    0:Turn off counting

    P12

    CAd

    Current correction

    +10%

    -10%

    0

    0.5%

    A

    Long press setting is not recommended

    P13

    FAd

    Frequency correction

    +2.5%

    -2.5%

    0

    0.1%

    Hz

    Modifying this value will affect the accuracy of the timer

    P14

    FPd

    Rapid power failure protection

    on

    off

    on

     

    MS

     

    P15

    dS

    Display mode

    3

    1

    1

    1

     

    1:Standards

    2:Manual switch

    3:Automatic switch

    P16

    Ar

    Automatic reset

    on

    off

    on

     

     

    on:Self-recovery

    off:Manual recovery

    P17

    Act

    Action/knife mode

    on

    off

    on

     

     

    on:Protector working properly

    off:knife mode

    P18

    EC

    Energy saving mode

    on

    off

    off

     

     

    on:Open

    off:Close

    P19

    Loc

    Setup lock password

    999

    000

    112

    1/10

     

    When this value is not 112,you can only view the parameter and cannot set it

    Standby InterfaceStandby Interface
    1. Standby Interface
    After power on, the digital tube will display current grid voltage and load current, e.g.: 220V 63.0A.

    2. Enter Setting Mode
    Press and hold the SET button for 3 seconds to enter parameter setting mode. The digital tube displays the first parameter code, e.g. P-1.

    3. Select Parameter
    Press ▲ or ▼ buttons to browse parameters. Find the parameter to set, e.g. P-3 (overvoltage protection point).

    4. Adjust Value
    Press SET button again to enter value adjustment. Use ▲ or ▼ to modify the value. Press and hold SET to save and move to next parameter.

    Product Specification & Installation

    Standby Interface
    Power-on self-test:
    Digital tube displays "888" and LED indicator lights up for 1 second on startup.

    Status display:
    The first digit shows overvoltage status, second shows undervoltage status, third shows overcurrent status.

    LED indicators:
    RUN (green) - operation; ALM (red) - protection alarm; OUTPUT (yellow) - output status.

    Frequency display:
    Press table to display current grid frequency (50Hz/60Hz).

    Standard dimensions:
    Width 36mm, Height 80mm, Depth 45mm. Compatible with standard distribution boxes.

    Terminals:
    Anti-loosening screw terminals, supporting up to 16mm² wire.

    Wiring and shape dimensions

    Wiring and shape dimensions

    Product display

    ELQ5-40 VA
    ELQ10-63 VA
    ELQ12-40 VA
    ELQ16-63

    Leave Your Message