ALBO Residual Current Operated Circuit Breaker(RCBO)
Product Details
Product Descriprion
The ALBO RCBOs provide integrated protection against earth leakage, overload, and short circuits in both 1P+N and 3P+N configurations, meeting the requirements of diverse applications from home use to large-scale engineering and wholesale distribution. Compliant with EN IEC 61009-1, they offer a breaking capacity of 6kA and support both B and C tripping characteristics for different inrush conditions. With adjustable sensitivity from 10mA to 300mA and rated currents from 3A to 40A, these devices enable tailored safety solutions for both shock and fire prevention in any installation.
Designed for 35mm DIN rails with a compact two-module width, the RCBOs feature lug or pin terminals and include clear specifications for conductor cross-sections and tightening torque, supporting consistent assembly in mass-produced distribution panels. They trip within 0.04 seconds at 30mA leakage, ensuring rapid response even in high-demand commercial circuits. With an IP20 rating and slim profile, they are ideal for use in residential and commercial distribution boards to protect sockets, lighting, HVAC, and sensitive equipment in both small-scale and large-scale projects.
Application
|
Standard |
Confirming to EN/IEC 61009-1 |
|
Breaking capacity |
6kA |
|
Protection |
Ground fault,overcurrent and short circuit |
|
Rated current,In |
3,6,10,16,20,25,32,40A |
|
Operating,Ln |
10,30,100,300mA |
|
Characteristic |
B.C |
|
Rated residual current operated making & breaking capacity l△m |
500A |
|
Rated residual non-operated current I△no |
0.5I△n |
|
Rated impulse withstand voltage Uimp |
4000V |
|
Number of poles |
1P+N |
|
Rated voltage |
230VAC |
|
Protection degree |
-25℃~+40℃ |
|
Residual current off-time |
≤0.1 sec. |
|
Type of trip Ground fault Over current |
Electro-magnetic Thermal-magnetic |
|
Protection degree |
IP20 |
|
Mount |
On 35mm DIN rail |
|
Width |
2 modules |
|
Terminal |
Lug type and Pin type |
|
Type |
AC,A Type B Type |
Curves
Breaking time of residual current
| In(A) | I△n (A) | Max.Breaking times | |||
| I△n | 2I△n | 5I△n | 5A,10A,20A,50A,100A,200A, | ||
| 3~40 | 0.01,0.03,0.1,0.3 | 0.1s | 0.08s | 0.04s | 0.04s |
Wiring
The suitable conductors should be used for connection, see table below for relative parameters.
| Rated current In(A) | Cross section area S(mm²) | Tightening torque(N.m) |
| 3~6 10 16~20 25 32 40 |
1 1.5 2.5 4 6 10 |
2 2 2 2 2 2 |
Overall and mounting dimensions
Product display
Product video
Features
✅B/C Dual-Curve Protection: Thermal-magnetic tripping for precise overload and fast fault response, stable under continuous commercial/industrial use.
✅Customizable Ratings for Projects: 3-40A current ratings + 10-300mA sensitivity, tailored to fit different engineering and wholesale order requirements.
✅Reliable Fast Tripping: ≤0.1s certified response, meeting safety standards for both home and large-scale commercial circuits.
✅Bulk Assembly Friendly Design: 2-module DIN rail size with universal terminals, ideal for mass production of distribution panels.