ALFR RCCB
Product Details
Product Descriprion
The ALFR RCCB series supports multiple rated currents ranging from 16A to 100A, designed for residential, commercial, and industrial distribution systems. It features an electromagnetic release mechanism and meets EN/IEC 61008-1 standards. The Type S model incorporates a minimum 40ms time delay to prevent nuisance tripping, making it suitable as a main switch or for use with Class II surge protectors.
Featuring a contemporary design, the product supports conductor connections up to 35mm² and can be securely mounted on DIN rails. A dual-color contact position indicator (red for closed, green for open) enhances operational safety, and all models are capable of withstanding current surges of up to 5kA. Its user-friendly wiring, compatible with busbars and pin-type terminals, and IP20 protection rating ensure reliable performance in diverse environments.
Performance includes rigorous endurance testing (on-load/off-load operating cycles) and precise breaking time requirements, tailored to the leakage type and current values. The Type S breaker provides selective protection, significantly reducing unnecessary power outages while meeting automatic disconnection time requirements of 0.2s or 0.4s, delivering essential reliability for demanding residual current protection scenarios.
Application
|
Standard |
Confirming to EN/IEC61008-1 |
|
Rated conditional short-circuit current,Inc |
6kA、10kA |
|
Protection |
Ground fault |
|
Rated current,In |
16,25,32,40,63,80,100A |
|
Number of poles |
2P(1P+N),4P(3P+N) |
|
Rated sensitivity currents,Ln |
10,30,100,300mA |
|
Rated residual non-operating current |
0.5XI△n |
|
Rated impulse withstand voltage Uimp |
6000V |
|
Rated voltages 2pole 4pole |
230VAC |
|
230/400VAC |
|
|
Protection degree |
-25°C~+40℃ |
|
Residual current off-time at I△n |
≤0.1s |
|
Rated residual current making &breaking capacity,I△m |
500A for In=16,25,32,40A 630A for In=63,80,100A |
|
Type of trip |
Electro-magnetic release |
|
Type of terminal |
Lug type and Pin type |
|
Terminal capacity |
Cables up to 35mm² |
|
Protection degree |
IP20 |
|
Installation |
35mm DIN rail |
|
Residual current operating characteristic AC,A,S |
|
Product display
Endurance
| In | Operating cycles | Operating frequency (operations/h) | |
| On-load operating cycles | Off-load operating cycles | ||
| 16,25,32 | 2000 | 2000 | 240 |
| 40,63,80,100 | 2000 | 1000 | 120 |
Breaking time of residual current
|
Max.breaking time |
||||||
|
Leakage type |
In(A) |
IΔn(A) |
IΔn |
2IΔn |
5IΔn |
5-500A |
|
A,AC |
16,25,32,40,63,80,100 |
0.01,0.03,0.1,0.3 |
0.1s |
0.08s |
0.04s |
0.04s |
|
S |
0.1,0.3 |
0.13s-0.5s |
0.06-0.02s |
0.05-0.15s |
0.05-0.15s |
|
Wiring
The suitable conductors should be used for connection,see table below for relative parameters.
| Rated current In(A) | Nominal cross section current area of lead(mm²) |
Tightinge torque(Nm) | |
| 25 | 4 | M6 2.5 | |
| 32 | 6 | ||
| 40 | 10 | ||
| 63 | 16 | ||
| 80 | 25 | ||
| 100 | 35 | ||
Features
When designing residual current devices,manufacturing technology and type of routine tests,the IEC/EN 61008 standards were considered.Important features are:
✓ Up to date design
✓ User-friendly connection of conductors and busbars
✓ Resistance to current surges;unwanted tripping excluded
✓ Simple and solid fixing to a 35 mm mounting rail in compliance with EN 60715
✓ Additional colour display of main contacts position(red:contacts closed, green: contacts open)