ALFR Residual Current Circuit Breaker(RCCB)
Product Details
Product Descriprion
The ALFR RCCB series offers Type A, AC, and S residual current circuit breakers, designed for residential, commercial, and industrial distribution systems, complying with EN/IEC 61008-1 standards. With a rated conditional short-circuit current of up to 10kA and multiple rated currents from 16A to 100A, the product features an electromagnetic release mechanism. The Type S variant incorporates a minimum non-operation time delay of 40ms to prevent unwanted tripping, making it suitable as a main switch or for use with Class II surge protectors.
Featuring a modern design, the product supports connections with conductors up to 35mm² and secure mounting via DIN rails. A dual-color contact position indicator (red for closed, green for open) enhances operational safety, while all models offer resistance to current surges up to 5kA. With user-friendly wiring compatible with busbars and pin-type terminals, and an IP20 protection rating, it ensures reliable performance in diverse environments.
Performance parameters include rigorous endurance tests (on-load/off-load operating cycles) and precise breaking time requirements (adjusted based on leakage type and current values). The Type S breaker provides selective protection, significantly reducing unnecessary power interruptions while meeting automatic disconnection time conditions of 0.2s or 0.4s, delivering critical reliability for high-demand residual current protection scenarios.
Application
|
Standard |
Confirming to EN/IEC61008-1 |
|
Rated conditional short-circuit current,Inc |
6kA、10kA |
|
Protection |
Ground fault |
|
Rated current,In |
16,25,32,40,63,80,100A |
|
Number of poles |
2P(1P+N),4P(3P+N) |
|
Rated sensitivity currents,Ln |
10,30,100,300mA |
|
Rated residual non-operating current |
0.5XI△n |
|
Rated impulse withstand voltage Uimp |
6000V |
|
Rated voltages 2pole 4pole |
230VAC |
|
230/400VAC |
|
|
Protection degree |
-25°C~+40℃ |
|
Residual current off-time at I△n |
≤0.1s |
|
Rated residual current making &breaking capacity,I△m |
500A for In=16,25,32,40A 630A for In=63,80,100A |
|
Type of trip |
Electro-magnetic release |
|
Type of terminal |
Lug type and Pin type |
|
Terminal capacity |
Cables up to 35mm² |
|
Protection degree |
IP20 |
|
Installation |
35mm DIN rail |
|
Residual current operating characteristic AC,A,S |
|
Product display
Endurance
| In | Operating cycles | Operating frequency (operations/h) | |
| On-load operating cycles | Off-load operating cycles | ||
| 16,25,32 | 2000 | 2000 | 240 |
| 40,63,80,100 | 2000 | 1000 | 120 |
Breaking time of residual current
|
Max.breaking time |
||||||
|
Leakage type |
In(A) |
IΔn(A) |
IΔn |
2IΔn |
5IΔn |
5-500A |
|
A,AC |
16,25,32,40,60,80,100 |
0.03,0.1,0.3 |
0.1s |
0.08s |
0.04s |
0.04s |
|
S |
0.1,0.3 |
0.13s-0.5s |
0.06-0.02s |
0.05-0.15s |
0.05-0.15s |
|
Wiring
The suitable conductors should be used for connection,see table below for relative parameters.
| Rated current In(A) | Nominal cross section current area of lead(mm²) |
Tightinge torque(Nm) | |
| 25 | 4 | M6 2.5 | |
| 32 | 6 | ||
| 40 | 10 | ||
| 63 | 16 | ||
| 80 | 25 | ||
| 100 | 35 | ||
Features
When designing residual current devices,manufacturing technology and type of routine tests,the IEC/EN 61008 standards were considered.Important features are:
✓ Up to date design
✓ User-friendly connection of conductors and busbars
✓ Resistance to current surges;unwanted tripping excluded
✓ Simple and solid fixing to a 35 mm mounting rail in compliance with EN 60715
✓ Additional colour display of main contacts position(red:contacts closed, green: contacts open)
✓ Type S: Selective type, RCD with non-operation time of atleast 40 ms
✓ High resistance to peak current up to 5 kA (IEC standardsrequire 3 kA).
✓ Meets conditions for tripping time 0.4 or 0.2 s (automatic disconnection).
✓ Type S is used as main circuit breaker or in combinationwith class II (C) surge voltage protectors.
✓ Significantly reduces unwanted trippings.