EATS-G Automatic Transfer Switch
Product Details
Product Descriprion
The EATS-G Automatic Transfer Switch represents cutting-edge PC-level technology that integrates switching mechanisms with intelligent logic control for seamless power management. Engineered for AC 50Hz systems up to 440V, this robust device handles heating currents from 100A to an impressive 3200A, meeting diverse power distribution requirements. Its core innovation lies in the true electromechanical integration, featuring voltage monitoring, communication interfaces, and dual mechanical/electrical interlocks for maximum safety.
The switch offers multiple operational modes: fully automatic transfer upon mains failure (with return functionality), manual override with a distinctive strong "O" cutoff position, and remote control capability. The design incorporates practical safety features including an electric key lock for operation mode selection and a dedicated padlock mechanism for secure maintenance isolation. Comprehensive status indicators (HD1/HD2/HD3) provide real-time visibility of power conditions and switch positions. Detailed wiring diagrams cover various configurations including fire-protection and non-fire protection types (3P/4P), with clear terminal designations for easy installation. With a short-time withstand current rating of 100-120kA and conversion times tailored to different current ratings (0.5-2.45s), the EATS-G delivers reliable performance for critical infrastructure including data centers, medical facilities, and industrial plants. Professional installation is recommended to ensure optimal operation and safety compliance.
Main Technical Parameters
|
Rated heating current (A) |
100 |
160 |
250 |
400 |
630 |
1000 |
1250 |
1600 |
2000 |
2500 |
3200 |
|
|
Rated insulation voltage |
750V |
|
1000V |
|||||||||
|
Rated impulse withstand voltage |
8KV |
|
12KV |
|||||||||
|
Rated working current (A) |
AC-31A |
100 |
160 |
250 |
400 |
630 |
1000 |
1250 |
1600 |
2000 |
2500 |
3200 |
|
AC-35A |
100 |
160 |
250 |
400 |
630 |
1000 |
1250 |
1600 |
2000 |
2500 |
3200 |
|
|
AC-33A |
100 |
160 |
250 |
400 |
630 |
1000 |
1250 |
1600 |
2000 |
2500 |
3200 |
|
|
Rated short-time withstand current |
7KA |
9KA |
13KA |
50KA |
80KA |
55KA |
||||||
|
Rated limit short-circuit current |
100KA |
70KA |
100KA |
120KA |
80KA |
|||||||
|
Control power supply voltage |
DC24V、48V、110V AC220V |
|||||||||||
|
Conversion time (S) |
0.5 |
1 |
1.1 |
1.2 |
1.25 |
2.45 |
||||||
1、Rated working voltage (Ue):AC440V
2、Rated Connection Capacity (Arms):10le;
3、Rated breaking capacity (Arms):8le;
4、Control power supply voltage:DC24V、48V、110VAC 220V.
Product Model Definition
|
□ |
□ |
□ |
□ |
□ |
□ |
□ |
|
Enterprise characteristic number |
Product Name |
Shell level |
poles |
|
|
|
|
ELECO Electrical |
Pc level isolated dual power automatic transfer switch |
|
4P |
The "F" indicates the fire protection type,which is a three-stage type:main power supply – double split and one backup power supply. No "F" indicates the two-stage type:main power supply and one backup power supply (there are fire protection and non fire protection types below 630A,and all above 800A are fire protection types) |
"E" represents 2 in and 1 out,with the main and backup power supply links on the load side integrated,making it convenient for customers to install |
"Z" represents intelligent,split type controller;Y701 controller - with functions such as over-voltage,undervoltage,phase loss,and starting the generator;Y702 controller – has functions such as over-voltage,undervoltage,phase loss,generator startup,485 communication,etc. |
Switch Structure Description
1. Electric key lock:control switch internal control line power supply,when the electric lock is opened,the switch can achieve automatic,operational control,strong"O"operation:when the electric lock is closed,the switch can only be manually operated.
2. Operating handle:When manually operating with the operating handle,the electric lock must be closed first.
3. The mechanism padlock:special maintenance,that is,first use the operating handle to make the switch in the"0"stop position,and then pick up the padlock mechanism and padlock,can be repaired (pick up the padlock will cut off the internal control power supply of the switch,the switch can not be automatic,and can not achieve manual).
4. Indicator:indicates the working status of the switch position.
Usage Method
(1)Switch Function
1. Automatic function:when the common power supply is cut off,the switch automatically switches to the standby power supply;When the usual power supply returns to normal,the switch automatically returns to the usual power supply.
2. Strong"0"function:start the strong "0"button,the switch will cut off the dual power supply.
3. Remote control function:that is,remote control,press the""file button:the common power supply works;Press the"“button,the standby power supply works:press the"0"button,the dual power supply is cut off.
4. Please select the switch function according to the need,and wiring according to the corresponding function 5,please specify the switch model,current specifications and required functions when ordering
⑵ Letter and symbol description
1) C1 and N1are the common power supply live line and neutral line respectively,C2 and N2 are the standby power supply live line and neutral line respectively.HL1and HL2 are the common power supply and the standby power supply respectively.HD1,HD2,HD3 are the common power supply,standby power input indicator and fire(double)indicator respectively.FU1 and FU2 are2A fuses.
2) 101-106 and 201-206 are automatic conversion secondary terminals.
3) 301-306 is the automatic switch external indicator terminal.
4) Automatic wiring mode 201,206 must be short-circuited.
5) Forced"0"contact(passive)can also input DC24V power supply:
6) K1 is the output of the power generation signal(when commonly used out of power).
7) SA is the automatic/manual function selection switch,SB1 and SB2 are the common power supply respectively,and the standby power manual input button(passive contact).
Terminal Wiring Operating Method
Use a small flathead screwdriver to apply downward force as shown in the diagram, and insert the wire as shown in the diagram
Wiring Diagram
Correct Installation Method of Switch
External Terminal Wiring Diagram
1. Non fire type wining method(3Pand 4P):
Below 630A (including 630AJ,there are two types:fire type and non fire type.Above 630A (excluding),all are fire type.

2、100A(fire protection type)~3200A automatic conversion wiring method (all applicable to 3P and 4P)

3、100A (fire protection type)~3200A fully automatic+forced"0"(both power sources are disconnected)wiring method:

4、100A(fire protection type)-3200A wiring terminal diagram:

100~3200 fully automatic+generator signal output wiring method

Fully automatic+manual(remote control)wiring method
Appearance and Installation Dimensions

|
specification |
Installation size |
||||||||||||||||||||||
|
In |
A |
A1 |
B |
B1 |
C |
E |
G |
H |
J |
K |
L |
N |
O |
P |
R |
S |
T |
U |
V |
ΦX |
Y |
Y1 |
Z |
|
100A/3 |
235 |
232 |
106 |
105 |
150 |
140 |
115 |
19 |
222 |
84 |
7 |
83 |
142.5 |
30 |
14 |
18 |
2.5 |
103 |
13 |
6 |
41.5 |
93 |
2 |
|
100A/4 |
280 |
244 |
107 |
105 |
150 |
140 |
115 |
19 |
226 |
84 |
7 |
83 |
142.5 |
30 |
14 |
18 |
2.5 |
103 |
13 |
6 |
41.5 |
93 |
2 |
|
160A/3 |
292 |
270 |
140 |
142 |
213 |
200 |
145 |
10 |
254 |
117 |
7 |
93 |
192 |
36 |
20 |
25 |
3.5 |
127 |
21 |
9 |
55.5 |
127 |
4 |
|
160A/4 |
360 |
303 |
140 |
142 |
213 |
200 |
145 |
10 |
285 |
117 |
7 |
93 |
192 |
36 |
20 |
25 |
3.5 |
127 |
21 |
9 |
55.5 |
127 |
4 |
|
250A/3 |
356 |
312 |
170 |
142 |
216 |
208 |
145 |
6 |
293 |
103 |
7 |
93 |
250 |
50 |
25 |
28 |
3.5 |
141 |
29 |
11 |
58 |
131 |
9 |
|
250A/4 |
420 |
362 |
180 |
142 |
216 |
208 |
145 |
6 |
343 |
103 |
7 |
93 |
250 |
50 |
25 |
28 |
3.5 |
141 |
29 |
11 |
58 |
131 |
9 |
|
400A/3 |
530 |
370 |
270 |
222 |
286 |
275 |
245 |
20 |
365 |
179 |
9 |
97 |
268 |
65 |
32 |
37 |
5 |
222 |
38 |
11 |
83 |
193 |
6 |
|
400A/4 |
590 |
440 |
270 |
222 |
286 |
275 |
245 |
20 |
425 |
179 |
9 |
97 |
328 |
65 |
32 |
37 |
5 |
222 |
38 |
11 |
83 |
193 |
6 |
|
630A/3 |
530 |
370 |
270 |
222 |
286 |
275 |
245 |
20 |
365 |
179 |
9 |
97 |
268 |
65 |
40 |
45 |
6 |
222 |
38 |
11 |
83 |
193 |
14 |
|
630A/4 |
590 |
440 |
270 |
222 |
286 |
275 |
245 |
20 |
425 |
179 |
9 |
97 |
328 |
65 |
40 |
45 |
6 |
222 |
38 |
11 |
83 |
193 |
14 |
|
800-1000A 3p |
785 |
520 |
380 |
250 |
351 |
340 |
360 |
20 |
503 |
220 |
11 |
88 |
415 |
120 |
60 |
64 |
8 |
250 |
59 |
13 |
109 |
254 |
39 |
|
800-1000A 4p |
1080 |
634 |
380 |
250 |
351 |
340 |
540 |
20 |
613 |
220 |
11 |
88 |
529 |
120 |
60 |
64 |
8 |
250 |
59 |
13 |
109 |
254 |
39 |
|
1250-1600A 3p |
785 |
520 |
380 |
250 |
351 |
340 |
360 |
20 |
503 |
220 |
11 |
88 |
415 |
120 |
80 |
68 |
8 |
250 |
59 |
13 |
110 |
255 |
43 |
|
1250-1600A 4p |
1080 |
634 |
380 |
250 |
351 |
340 |
540 |
20 |
617 |
220 |
11 |
88 |
529 |
120 |
80 |
68 |
8 |
250 |
59 |
13 |
110 |
255 |
43 |
|
2000A/3 |
785 |
535 |
423 |
|
560 |
|
360 |
|
408 |
|
|
|
490 |
|
80 |
81 |
10 |
|
30 |
|
|
113 |
|
|
2000A/4 |
1080 |
650 |
423 |
|
560 |
|
540 |
|
523 |
|
|
|
605 |
|
80 |
81 |
10 |
|
30 |
|
|
113 |
|
|
2500A/3 |
785 |
535 |
433 |
|
560 |
|
360 |
|
408 |
|
|
|
490 |
|
80 |
81 |
15 |
|
30 |
|
|
118 |
|
|
2500A/4 |
1080 |
650 |
433 |
|
560 |
|
540 |
|
523 |
|
|
|
605 |
|
80 |
81 |
15 |
|
30 |
|
|
118 |
|
|
3200A/3 |
785 |
535 |
443 |
|
560 |
|
360 |
|
408 |
|
|
|
490 |
|
80 |
81 |
20 |
|
30 |
|
|
123 |
|
|
3200A/4 |
1080 |
650 |
433 |
|
560 |
|
540 |
|
523 |
|
|
|
605 |
|
80 |
81 |
20 |
|
30 |
|
|
123 |
|