ELBO Residual Current Operated Circuit Breaker(RCBO)
Product Details
Product Descriprion
The ELBO RCBO, or Residual Current Operated Circuit Breaker, complies with EN IEC 61009-1 and integrates protection against overloads, short circuits, and earth faults using both Type B and C tripping characteristics. It provides multi-layered safety by preventing direct and indirect contact and mitigating fire risks caused by insulation faults, making it suitable for both residential and commercial power distribution systems, including engineering projects and wholesale applications. It also allows for safe circuit isolation.
With a high breaking capacity of 10kA at 240V AC, the device employs dual tripping mechanisms: a thermal unit for overloads and an electromagnetic release for rapid short-circuit interruption in milliseconds. Rated currents range from 6A to 40A, segmented into specific steps to meet diverse project requirements. The residual current tripping time is hierarchical, operating within 0.1 seconds at the rated differential current and within 0.04 seconds at five times that value, ensuring reliable performance even in high-demand installations.
Conductor sizes correspond to current ratings, from 1mm² for 6A up to 10mm² for 40A. Terminals are tightened to a standard torque of 2N·m, or 2.5N·m for the 25A model. The compact modular design allows for easy installation on 35mm DIN rails and features clear ON/OFF indicators, ideal for mass assembly in distribution panels and large-scale projects. It is optimized to protect against sinusoidal AC earth faults in building electrical systems.
Technical data
|
Standard |
EN/IEC61009-1 |
|
Breaking Capacity |
6kA,10kA |
|
Number of poles |
1P+N(1 module) |
|
Rated current,In |
6,10,13,16,20,25,32,40A |
|
Rated voltage |
240VAC |
|
Rated Tripping Current |
10,30,100,300mA |
|
Residual current off time |
≤0.1s |
|
Characteristic |
B,C Curve |
|
Electrical endurance |
4000 |
|
Mechanical endurance |
10000 |
|
Ambient temperature(℃) |
-25~+40,Max.95%humidity |
|
Connection terminal |
Flexible conductor 16mm² Rigid conductor 25mm² |
|
Type of terminal |
Lug type and Pin type |
|
Width |
17.8mm |
Curves
Breaking time of residual current
|
In(A) |
I△n(A) |
Max.breaking time |
|||
|
I△n |
2I△n |
5I△n |
5A,10A,20A,50A,100A,200A,500A |
||
|
6-40 |
0.01,0.03,0.1,0.3 |
0.1s |
0.08s |
0.04s |
0.04s |
Wiring
The suitable conductors should be used for connection,see table for relative parameters.
|
Rated current In(A) |
Cross section area (mm²) |
Tightening torque(N.m) |
|
6 |
1 |
2 |
|
10 |
1.5 |
2 |
|
16~20 |
2.5 |
2 |
|
25 |
4 |
2 |
|
32 |
6 |
2 |
|
40 |
10 |
2 |
Product display
Product video
Features
1. Switching and isolation function for safe circuit maintenance in both household and commercial installations.
2. Protection against overload and short-circuit currents, with stable performance designed for continuous use in engineering projects and bulk applications.
3. Protection against the effects of sinusoidal alternating earth fault currents, meeting international standards for commercial and industrial electrical systems.
4. Protection against indirect contacts and additional protection against direct contacts, helping reduce fire hazards caused by insulation faults in both residential and large-scale buildings.
5. Suitable for use in residential buildings, commercial facilities, and distribution boards for wholesale and engineering projects.