ELV□-M Series Motor Protection Circuit Breaker
Product Details
Product Descriprion
The ELV□-M series motor protection circuit breakers are designed for AC 50/60Hz circuits with voltages up to 660V and currents from 0.1A to 80A. They deliver triple protection by integrating overload and short-circuit protection for motors under AC3 loads, enabling direct full-voltage motor starting, and providing fault protection for circuits and equipment within power distribution systems. These breakers are widely used in industrial motor control applications such as fans and pumps, as well as in global grid environments requiring voltage compatibility from 220V to 660V.
Electrical specifications support multiple voltages including 220V, 380V, 415V, 440V, 500V and 660V, with current ratings spanning 0.1A to 80A to match standard motor power levels across voltages. The breakers support frequent start-stop operations and incorporate optimized overload balance protection for varying load conditions. For critical performance parameters such as breaking capacity, users should refer to the product manual.
Application
ELV□-M series motor protection circuit breakers is mainly used for the overload and short circuit protection of the motor in AC 50/60Hz,up to 660V,0.1-80A power circuit,as a full voltage starter to start and cut off the motor,under the AC3 load or for the overload and short circuit protection of the circuit and power equipment in the power distribution network.
Specifications
|
Type |
Rated or scale of rated current(A) |
Rated standard power of 3-phase motors 50/60Hz in category AC-3 |
|||||
|
220V |
380V |
415V |
440V |
500V |
660V |
||
|
KW |
KW |
KW |
KW |
KW |
KW |
||
|
ELV2-M01 |
0.1-0.16 |
-- |
-- |
-- |
-- |
-- |
-- |
|
ELV2-M02 |
0.16-0.25 |
-- |
-- |
-- |
-- |
-- |
-- |
|
ELV2-M03 |
0.25-0.4 |
-- |
-- |
-- |
-- |
-- |
-- |
|
ELV2-M04 |
0.4-0.63 |
|
|
|
|
|
0.37 |
|
ELV2-M05 |
0.63-1 |
|
|
|
0.37 |
0.37 |
0.55 |
|
ELV2-M06 |
1-1.6 |
|
0.37 |
|
0.55 |
0.75 |
1.1 |
|
ELV2-M07 |
1.6-2.5 |
0.37 |
0.75 |
0.75 |
1.1 |
1.1 |
1.5 |
|
ELV2-M08 |
2.5-4 |
0.75 |
1.5 |
1.5 |
1.5 |
2.2 |
3 |
|
ELV2-M10 |
4-6.3 |
1.1 |
2.2 |
2.2 |
3 |
3.7 |
4 |
|
ELV2-M14 |
6-10 |
2.2 |
4 |
4 |
4 |
5.5 |
7.5 |
|
ELV2-M16 |
9-14 |
3 |
5.5 |
5.5 |
7.5 |
7.5 |
9 |
|
ELV2-M20 |
13-18 |
4 |
7.5 |
9 |
9 |
9 |
11 |
|
ELV2-M21 |
17-23 |
5.5 |
11 |
11 |
11 |
11 |
15 |
|
ELV2-M22 |
20-25 |
5.5 |
11 |
11 |
11 |
15 |
18.5 |
|
ELV2-M32 |
24-32 |
7.5 |
15 |
15 |
15 |
18.5 |
26 |
|
ELV3-M06 |
1-1.6 |
-- |
0.37 |
-- |
0.55 |
0.75 |
1.1 |
|
ELV3-M07 |
1.6-2.5 |
0.37 |
0.75 |
1.1 |
1.1 |
1.1 |
1.5 |
|
ELV3-M08 |
2.5-4 |
0.75 |
1.5 |
1.5 |
1.5 |
2.2 |
3 |
|
ELV3-M10 |
4-6 |
1.1 |
2.2 |
2.2 |
3 |
3.7 |
4 |
|
ELV3-M14 |
6-10 |
2.2 |
4 |
4 |
4 |
5.5 |
7.5 |
|
ELV3-M20 |
10-16 |
4 |
7.5 |
7.5 |
7.5 |
10 |
11 |
|
ELV3-M25 |
16-25 |
5.5 |
11 |
11 |
11 |
15 |
18.5 |
|
ELV3-M40 |
25-40 |
11 |
18.5 |
22 |
22 |
25 |
33 |
|
ELV3-M63 |
40-63 |
15 |
30 |
33 |
33 |
40 |
55 |
|
ELV3-M80 |
56-80 |
22 |
40 |
45 |
45 |
55 |
63 |
|
Type |
|
230/240V |
400/415V |
440V |
500V |
690V |
|||||
|
ELV2-M |
|
Icu |
Ics %(1) |
Icu |
Ics %(1) |
Icu |
Ics %(1) |
Icu |
Ics %(1) |
Icu |
Ics %(1) |
|
|
A |
KA |
|
KA |
|
KA |
|
KA |
|
KA |
|
|
01-06 |
01-06 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
75 |
|
07 |
2.5 |
- |
- |
- |
- |
- |
- |
- |
- |
3 |
75 |
|
08 |
4 |
- |
- |
- |
- |
- |
- |
- |
- |
3 |
75 |
|
10 |
6.3 |
- |
- |
- |
- |
50 |
100 |
50 |
100 |
3 |
75 |
|
14 |
10 |
- |
- |
100 |
- |
10 |
100 |
10 |
100 |
3 |
75 |
|
16 |
14 |
- |
- |
15 |
50 |
8 |
50 |
6 |
75 |
3 |
75 |
|
20 |
18 |
- |
- |
15 |
50 |
8 |
50 |
6 |
75 |
3 |
75 |
|
21 |
23 |
50 |
100 |
15 |
40 |
6 |
50 |
4 |
75 |
3 |
75 |
|
22 |
25 |
50 |
100 |
15 |
40 |
6 |
50 |
4 |
75 |
3 |
75 |
|
32 |
32 |
50 |
100 |
10 |
50 |
6 |
50 |
4 |
75 |
3 |
75 |
|
Type |
|
230/240V |
400/415V |
440V |
500V |
690V |
|||||
|
ELV2-M |
|
aM |
gl |
aM |
gl |
aM |
gl |
aM |
gl |
aM |
gl |
|
|
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
|
01-06 |
01-06 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|
07 |
2.5 |
- |
- |
- |
- |
- |
- |
- |
- |
36 |
20 |
|
08 |
4 |
- |
- |
- |
- |
- |
- |
- |
- |
25 |
32 |
|
10 |
6.3 |
- |
- |
- |
- |
50 |
63 |
50 |
63 |
32 |
40 |
|
14 |
10 |
- |
- |
- |
- |
50 |
63 |
50 |
63 |
32 |
40 |
|
16 |
14 |
- |
- |
63 |
80 |
50 |
63 |
50 |
63 |
40 |
50 |
|
20 |
18 |
- |
- |
63 |
80 |
50 |
63 |
50 |
63 |
40 |
50 |
|
21 |
23 |
80 |
100 |
80 |
100 |
63 |
80 |
50 |
63 |
40 |
50 |
|
22 |
25 |
80 |
100 |
80 |
100 |
63 |
80 |
50 |
63 |
40 |
50 |
|
32 |
32 |
80 |
100 |
80 |
100 |
63 |
80 |
50 |
63 |
40 |
50 |
|
Operation performance for motor protection circuit breaker |
||||||||||||||||
|
Serial no. |
Rated current Inm(A) |
Operating cycle frequency(times/h) |
Operating cycle electric life(times0 |
Mechanical life(times) |
overall( times) |
|||||||||||
|
1 |
ELV2-M |
120 |
2000 |
10000 |
1200 |
|||||||||||
|
2 |
ELV3-M |
120 |
2000 |
10000 |
1200 |
|||||||||||
|
Overload balance characteristics |
||||||||||||||||
|
Step no. |
Test current(A) |
Start situation |
Limited time |
Pre-engage result |
Ambient air temperature |
|||||||||||
|
1 |
1.05 |
Cold state |
t≥2h |
Non-trip |
□20℃±2℃ |
|||||||||||
|
2 |
1.2 |
hot state(The current rise steadily to a fixed value after step 1) |
t<2h |
trip |
□20℃±2℃ |
|||||||||||
|
3 |
1.5 |
It starts after the heat balance of 1.0In current |
trip 10A t<2 min |
trip |
□20℃±2℃ |
|||||||||||
|
grade 10 t<4min |
trip |
□20℃±2℃ |
||||||||||||||
|
4 |
7.2 |
Cold state |
trip 10A 2s<t≤10s |
trip |
□20℃±2℃ |
|||||||||||
|
grade 104s≤t≤10 |
trip |
□20℃±2℃ |
||||||||||||||
|
Overload non-balance characteristics |
|
|||||||||||||||
|
Step no. |
Test current (A) |
Start situation |
Limited time |
Pre-engage result |
Ambient air temperature |
|||||||||||
|
Two phases |
Third-phase |
|||||||||||||||
|
1 |
1.0 |
0.9 |
Cold state |
t≥2h |
Non-trip |
□20℃±2℃ |
||||||||||
|
2 |
1.15 |
0 |
hot state(The current rise steadily to a fixed value after step 1) |
t<2h |
trip |
□20℃±2℃ |
||||||||||
Features
1. Wide-Range Precision Protection:
Operates in AC 50/60Hz power circuits up to 660V voltage and 0.1-80A current range. This motor protection circuit breaker delivers dual overload and short-circuit protection for motors, covering equipment from micro to medium-large current applications.
2. High Durability & Long Lifespan:
The 120A model (ELV2-M/ELV3-M) achieves 10,000 electrical operations, 10,000 mechanical operations, and a combined lifespan of 12,000 cycles. This performance specification satisfies high-frequency industrial operation demands.
3. Multifunctional Integrated Application:
Functions as a full-voltage motor starter under AC-3 loads to control motor start/stop operations. Simultaneously protects distribution network circuits and power equipment against overload and short-circuit conditions, consolidating multiple functionalities into a single device.
4. Rigorous Overload Performance Verification:
Comprehensive testing validates reliability through balanced characteristics across 1.05In to 7.2In current ranges with cold/hot state response times measured to minute-level precision, plus unbalanced characteristic verification under abnormal conditions including two-phase 0.9In + one-phase 1.0In operation. All performance tests were conducted at controlled 20℃±2℃ ambient temperature.