EW7-2000 Air Circuit Breaker
ACB

EW7-2000 Air Circuit Breaker

EW Series Universal Circuit Breaker (hereinafter referred to as the circuit breaker) is applicable to the distribution network with AC 50 Hz, rated current 200 ~ 6300 A, rated insulation voltage 1000 V, rated working voltage 400 V and 690 V, and is used to distribute electric energy and protect the line and power supply equipment from the hazards of overload, under voltage, short circuit, single-phase grounding and other faults. And can also be use as a quarantine switch. The circuit breaker has a variety of protection functions, which can achieve high-precision selective protection, avoid unnecessary power outages, and improve the reliability and safety of power supply.  

630A and the following circuit breakers can be used for infrequent starting of the motor and play the role of protection function.

Compliant with standards:IEC60947‑2、GB/T 14048.2

    Product Details

    Product Descriprion

    The EW7-2000 is a universal air circuit breaker designed for AC 50Hz distribution networks, with a rated current range from 200 to 6300A and rated operational voltages of 400V/690V. It is primarily used to distribute electrical energy and protect lines and power supply equipment from hazards such as overload, under-voltage, short circuit, and single-phase ground faults. It can also function as an isolation switch. Its design complies with IEC60947-2 and GB/T 14048.2 standards, featuring high-precision selective protection to avoid unnecessary power outages and enhance power supply reliability and safety. Breakers rated 630A and below can also be used for the infrequent starting of motors.

    KP0A8762

    This breaker features high breaking capacity (up to 100kA), zero arc flashing, acceptance of both top and bottom cable entry, and a compact size. It is equipped with an intelligent over-current controller that provides multiple protection functions including long-time delay, short-time delay, instantaneous, and ground fault protections, which can be set to inverse-time or definite-time modes. The controller (3M/3H types) also measures and displays parameters like voltage, frequency, and power. Advanced models (2H/3H types) support Modbus and Device-net communication protocols for remote monitoring and integrated bus management. Various mechanical interlocks and drawer locks are available to ensure operational safety. Its performance is subject to derating as ambient temperature increases.

    The breaker must be installed under ambient temperatures ranging from -5°C to +40°C and at altitudes not exceeding 2000 meters, with a degree of protection of IP30/IP40 (when installed inside an enclosure). During installation, its vertical inclination must not exceed 5°. The provided installation dimension drawings detail the overall external dimensions and the precise cutout dimensions and positions (e.g., hole diameter φ12) required for busbar connections for the EW-2000 series fixed breakers (200-2000A, 3-pole/4-pole), providing clear mechanical guidance for correct installation and busbar wiring within switchgear.

    Scope of application

    Standard

    IEC60947‑2、GB/T 14048.2

    Breaking capacity

    Selective protection(Precise coordination)

    Protection

    Overload, Under voltage, Short circuit, Single-phase grounding

    Rated current In

    200-6300A(≤630A for motor protection)

    Rated operational voltage

    400V/ 690VAC

    Rated insulation voltage

    10000V

    Characteristics

    High-precision selective protection

    Isolation switch capability

    Functionality

    Power distribution

    Fault protection

    Unnecessary outage prevention

    Supply enhancement

    Improved reliability & safety

    Frequency

    50Hz

    Degree of protection

    IP30(IP40 when installed in cabinet)

    Altitude

    ≤2000m

    Mounting

    ≤5°vertical inclination

    Product characteristics

    High breaking rate, zero arc flying;

    Safety isolation function;

    Both upper and lower incoming lines are acceptable.

    Small in size;

    Detection and selective protection functions facilitate the selection of various requirements.

    The wiring methods are diverse, including horizontal and vertical mixed types, which are convenient for installation.

    The newly launched 3M and 3H type LCD screen display controllers, in addition to current display and protection, have added measurement and protection functions for voltage, frequency, phase sequence, power, etc., making their functions more powerful.

    Regional Selective Interlocking protection (ZSI) significantly reduces the area affected by power outages due to faults, achieving reliable protection.;

    It is equipped with various forms of mechanical interlocks (lever type and steel cable type), drawer locks, door interlocks and safety-guaranteed disconnection position locks to achieve the locking of circuit breakers.

    The 2H and 3H type intelligent controllers have communication networking and monitoring functions. They can adopt Mod bus and Device-net protocols, facilitating integrated bus management. It can achieve remote control, remote measurement, remote signaling and remote adjustment.

    Product display

    KP0A8736
    KP0A8739
    KP0A8741
    KP0A8751

    Technical Data & Performance

    1. Circuit Breaker Rating Current

    Frame Rating Rate Current Inm(A)

    Rated Current In(A)

    200 、 315 、 400 、 500 、 630 、 800 、 1000 、 1250 、 1600

    2000

    200 、 315 、 400 、 500 、 630 、 800 、 1000 、 1 250 、 1600 、 2000

    3200

    2000 、 2500 、 2900 、 3200

    4000

    3200 、 3600 、 4000

    6300

    4000 、 5000 、 6300

    2. The circuit breaker features a rated short-circuit breaking capacity, a specified short-time withstand current, and provides arc flash containment with no external arcing outside the circuit breaker enclosure.

    Frame Rating Rate Current Inm(A)

    Rated Ultimate Short-Circuit Breaking Capacity Icu(KA) O-CO

    400V

    55

    80

    1 20

    690V

    50

    65

    Rated Short-Circuit Making Capacity n x lcu (KA)/cos

    400V

    143/0 . 2

    176/0 . 2

    220/0 . 2

    220/0 . 2

    264/0 . 2

    690V

    105/0 . 25

    143/0 . 2

    Rated Service Short-Circuit Breaking Capacity lcs(KA)O-CO-CO

    400V

    42

    50

    65

    80

    690V

    50

    65

    Rated Short-Time Withstand Current

    lcw (KA) 1S , delay0 . 4S , O-CO

    400V

    42

    50

    65

    80

    690V

    50

    65

    Note: The breaking capacities in the table are identical for both upward and downward line terminals (directionally independent).

    3. The circuit breaker has a maximum power dissipation of 360 W under rated operating conditions, and its rated continuous current is subject to derating based on ambient temperature.

    environmental temperature℃
    3SW
    400A 630A 800A 1000A 1250A 1600A 2000A
    40 400A 630A 800A 1 000A 1 250A 1 600A 2000A
    50 400A 630A 800A 1 000A 1 250A 1550A 1 900A
    60 400A 630A 800A 1 000A 1 250A 1550A 1800A

    Note: Derating factor for 2500A frame and above is 0.9. For the 6300A frame, the 4000A rating does not require derating.

    4. Intelligent Overcurrent Controller: Protection Characteristics & Functions

    Overcurrent Controller Protection Characteristics

    a. Grouped settings logically & Tolerances

    ​Long-Time Delay Protection

    Short-Time Delay Protection

    Instantaneous Protection

    Ground Fault

    lr1

    lr2

    Tolerances

    lr3

    Tolerances

    lr4

    Tolerances

    (0 . 4-1)lnI (>=160A)

    (0 . 4 - 15)In (>=160A)

    ± 1 0%

    In 50KA(Inm = 2000A)

    In ~ 75KA(Inm =3200 ~ 4000A) In ~ 100KA(Inm = 6300A)

    ± 15%

    (0 . 2 - 1)In (>=160A)

    ± 1 0%

    Note: When all three protection stages are simultaneously enabled, their current settings must be non-overlapping to ensure coordinated tripping.

    b. The operating times for overcurrents within the range (1.05 to 2.0) x Ir1 are provided in Table 5.
    The time tolerance: ± 15% .
    Note: TL denotes the setting time for tripping at ​1.5 x Ir1; tL denotes the actual operating time.

    1.05lr1

    1.3lr1

    1.5lr 1setting time s

    15

    30

    60

    120

    240

    480

    >2h no-operation

    <1h operation

    2.0lr1 operation time(s)

    8 . 4

    16.9

    33 . 7

    67 . 5

    135

    270

    c. Short-Time Overcurrent Protection Characteristic
    The short-time delay over-current protection defaults to definite-time operation, but provides inverse-time characteristics (following Ts = 8·Ir/ts·I) at multiples ≤8xIr1 when required; above 8xIr1 it automatically switches to definite-time operation as defined in Table 6, with time tolerance ±15%.

    Delay Time s

    Returnable Time s

    0.1

    0 . 2

    0 . 3

    0 . 4

    0.06

    0 . 1 4

    0 . 23

    0 . 35

    EW-2000 3P/4P In=200-2000A Fixed circuit breaker installation size and external dimensions

    EW7-2000 Fixed Standard Busbar Horizontal Wiring(Standard configuration) (LEFT)
    EW7-2000 Fixed-Extended Busbar Horizontal Connection(Special Configuration)(RIGHT)

    EW7-2000-Air-Circuit-Breaker-1KP0A8762-3

    EW7-2000 3P/4P In=200-2000A Drawer circuit breaker installation size and external dimensions

    EW7-2000 Drawer-type Standard Busbar Horizontal Wiring(Standard configuration)(LEFT)
    EW7-2000 Drawer-type Busbar Horizontal Wiring(Special Configuration)(RIGHT)

    EW7-2000-Air-Circuit-Breaker-2KP0A8762-1