LKB-80WL IoT Smart Circuit Breaker
Product Details
Product Descriprion
The LKB-80WL delivers multi-scenario electrical protection with overload, short-circuit, and leakage protection, compatible with 230V/600V AC grids in industrial/commercial settings. Its breakthrough IoT remote control uses 12 protocols for real-time status monitoring, fault alerts, remote switching, and energy analytics, enhancing safety and operational efficiency.
It spans 16A–80A rated currents (16/20/32/40/50/63/80A) with 6kA breaking capacity, operating from -25°C to +55°C. Installation mandates compliance: uniform 2N·m terminal torque, conductor sizing per current (e.g., 16mm² for 50A, 25mm² for 80A), with strict bans on live-wire handling or wet-operation. Includes 35mm DIN rail dimensions and phase-wiring diagrams.
Embedded millisecond leakage response (≤0.1s tripping) and physical isolation ensure safety. The IoT module enables custom threshold alerts (e.g., voltage/temperature anomalies) and automated reports. Optimized for 24/7 risk prevention in smart buildings and grid management, backed by life cycle technical support per warranty terms.
Application
|
Rated Voltage(Uₙ) |
230V AC (1P+N, 2P); 400V AC (3P, 3P+N, 4P) |
|
Rated Current(Iₙ) |
6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A |
|
Residual Operating Current |
30mA, 50mA, 100mA, 300mA |
|
Residual Non-Operating Current |
0.5 × IΔn |
|
Residual Current Protection Type |
AC Type |
|
Number of Poles |
1P+N, 2P, 3P, 3P+N, 4P |
|
Instantaneous Trip Type |
B, C, D (Customizable per request) |
|
Rated Service Short-Circuit Breaking Capacity |
Ins=Ics=6 kA |
|
Rated Residual Making & Breaking Capacity |
500A (Iₙ ≤ 50A); 10 × Iₙ (Iₙ ≥ 63A) |
|
Remote Auto-Reclosing Time |
≤ 3 seconds |
|
Remote Auto-Tripping Time |
≤ 3 seconds |
|
Over-voltage Protection |
Trip: 270–280V; Reset: 245–255V |
|
Undervoltage Protection |
Trip: 160–170V; Reset: 180–190V |
|
Tightening Torque |
2.5 N·m |
|
Pollution Degree |
Level 2 |
|
Ingress Protection (IP) Rating |
IP20 |
|
Installation Category |
Category III |
1. Rated Service Short-Circuit Breaking Capacity
|
Rated current In(A) |
I△n(mA) |
I△n |
2I△n |
5I△n |
5A、10A、20A、50A、100A、200A、500A |
I△tb |
|
6~80 |
30、50、 100,300
|
0.1s |
0.05s |
0.04s |
0.04s |
0.04s |
2. Overcurrent Protection Characteristics
|
No |
Test current (A) |
Initial state |
Trip or No-trip keep time limits |
Result to be obtained |
Test ambient temperature |
Remarks |
||
|
1 |
1.13In |
Cold state |
t≥1h |
In≤63A |
No-trip |
30 ~35℃ |
|
|
|
t≥2h |
In>63A |
|||||||
|
2 |
1.45In |
Upon the Previous test |
t≤1h |
In≤63A |
Trip |
30 ~35℃ |
Setting current up to specified value steadily in 5s |
|
|
t≤2h |
In>63A |
|||||||
|
3 |
2.55In |
Cold state |
1s<t<60s |
In≤32A |
Trip |
30 ~35℃ |
|
|
|
1s<t<120s |
In>32A |
|||||||
|
4 |
B |
3In |
Cold state |
t>0.1s |
No-trip |
30 ~35℃ |
Current is connected by closing the auxiliary switch |
|
|
5In |
t<0.1s |
Trip |
||||||
|
5 |
C |
5In |
Cold state |
t>0.1s |
No-trip |
30 ~35℃ |
||
|
10In |
t<0.1s |
Trip |
||||||
|
6 |
D |
10In |
Cold state
|
t>0.1s |
No-trip |
30 ~35℃ |
||
|
|
14In |
t<0.1s |
Trip |
|
||||
3. Tripping Characteristic Curve
4. Mechanical & Electrical Endurance
|
Test item |
Times |
power factor |
Operating frequency |
|
Electrical life |
10000 |
cOsΦ=0.85~0.9 |
In≤32A,240times/h |
|
Mechanical life |
20000 |
|
5. Dimensions & Mounting Specifications

Product Display
6. Wiring
|
Rated current In (A) |
6 |
10 |
16、20 |
25 |
32 |
40、50 |
63 |
80 |
|
Cross section area of lead S mm² |
1 |
1.5 |
2.5 |
4 |
6 |
10 |
16 |
25 |
7. Product Features
7.1 Rated breaking capacity is high, up to 10kA.
7.2 The operating mechanism of the circuit breaker is an energy storage type free trip mechanism. The contacts close quickly, which overcomes the adverse effects caused by the speed of manual operation of the handle, greatly extending the service life of the product. During normal operation, the contacts can only remain in the closed or open position.
7.3 The combination terminal blocks with finger touch protection offer higher safety performance.
7.4 The shell and components are all made of imported high flame-retardant, high-temperature resistant and impact-resistant plastics from abroad.