Leave Your Message
MGR Series Residual Current Circuit Breaker(RCCB)
RCCB

MGR Series Residual Current Circuit Breaker(RCCB)

This IEC 61008-1 certified earth leakage breaker provides essential ground-fault protection with sensitivity settings of 10mA, 30mA, or 100mA. It is available in rated currents from 16A to 100A and offers both 2P and 4P configurations. Key features include a residual breaking capacity of 500A for units up to 40A and 630A for higher ratings, along with a 6000V impulse withstand voltage. The device trips within 0.1 seconds at its rated residual current and features dual lug and pin terminals compatible with cables up to 35mm². With IP20 protection and 35mm DIN rail mounting, it is ideal for enhancing electrical safety in residential and commercial distribution boards, as well as aging wiring renovation projects.

    Product Details

    Product Descriprion

    The MGR Series Residual Current Circuit Breaker provides reliable earth fault protection and is fully compliant with IEC 61008-1. It is available in both 2-pole and 4-pole configurations and utilizes an electromagnetic tripping mechanism for rapid leakage current interruption, with a maximum disconnection time of 0.1 seconds at the rated residual current. Rated for 6000V impulse voltage withstand, the device operates effectively in 240V and 415V AC systems.

    It offers an ultimate short-circuit breaking capacity of 6kA and supports a wide range of rated currents from 16A to 100A. With adjustable tripping thresholds spanning 0.03A to 500A, it ensures faster response at higher fault levels, interrupting within 0.04 seconds at five times the rated residual current. The breaker is endurance tested for 2000 operational cycles under both load and no-load conditions.

    Housed in flame-retardant and impact-resistant plastic with IP20 protection, it performs reliably even in polluted environments. Designed for 35mm DIN rail mounting, the terminals accept conductors up to 35mm² in both lug and pin types, with specified torque values such as 3.5N·m for 25mm² wiring. Its compact modular design, measuring 45mm per pole and 90.4mm in total height, saves valuable panel space. A grey operation lever provides clear ON/OFF status indication, and the unit operates without requiring auxiliary power.

    Application

    Standard

    Confirming to IEC61008-1

    Protection

    Ground fault

    Rated current,In

    16,25,32,40,63,80,100A

    Number of poles

    2(1+N),4(3+N)pole

    Rated sensitivity currents,I△n

    10,30,100mA

    Rated residual non-operating current

    0.5XI△n

    Rated impulse withstand voltage Uimp

    6000V

    Rated voltages 2pole 4pole

    240VAC

    240/415VAC

    Residual current off-time at I△n

    ≤0.1s

    Rated residual current making &breaking capacity,I△mA

    500A for In=16,25,32,40A 630A for In=63,80,100A

    Rated conditional short-circuit current,Inc

    6kA

    Type of trip

    Electro-magnetic release

    Type of terminal

    Lug type and pin type

    Terminal capacity

    Cables up to 35mm²

    Degree of protection

    IP20

    Installation

    35mm DIN rail

    Slot size

    45mm

    Product display

    MGR-1-1
    MGR-1-2
    MGR-4p

    Endurance

    In

    Operating cycles

    On-load operating cycles Off-load operating cycles

    Operating frequency

    (operations/h)

    16,25,32

    2000

    2000

    240

    40,63,80,100

    2000

    1000

    120

    Breaking time of residual current

    Breaking time of residual current

    In(A)

    IΔn(A)

    IΔn

    2IΔn

    5IΔn

    5A,10A,20A,50A,

    100A,200A,500A

    16,25,32,40,63,

    80,100

    0.01,0.03,0.1,0.3

    0.1s

    0.08s

    0.04s

    0.04s

    Max.Breaking time

    Wiring

    The suitable conductors should be used for connection,see table below for relative parameters.

    Rated current In(A)

    Nominal cross section area of lead(mm²)

    Tightening torque(N.m)

    16

    2.5

    2.5

    25

    4

    2.5

    32

    6

    2.5

    40

    10

    2.5

    63

    16

    2.5

    80

    25

    3.5

    100

    35

    3.5

    Features

    1. Without auxiliary power supply,the product is designed with strong immunity and extending protection range against residual current.

    2. With higher rated ultimate short circuit up to 6KA

    3. High reliable operation thanks to special design terminals.

    4. Even under the pollution environment,the working reliability of the product will never be changed

    5. Enclosure and functional parts made from imported plastics with flame-retardant,heat-resistant,and impulse-proof properties Convenient mounting

    6. More flexible and reliable operation with a handle

    Overall and mounting dimensions

    MGR-Overall-and-mounting-dimensions

    Leave Your Message