MGR Series Residual Current Circuit Breaker(RCCB)
Product Details
Product Descriprion
The MGR Series Residual Current Circuit Breaker provides reliable earth fault protection and is fully compliant with IEC 61008-1. It is available in both 2-pole and 4-pole configurations and utilizes an electromagnetic tripping mechanism for rapid leakage current interruption, with a maximum disconnection time of 0.1 seconds at the rated residual current. Rated for 6000V impulse voltage withstand, the device operates effectively in 240V and 415V AC systems.
It offers an ultimate short-circuit breaking capacity of 6kA and supports a wide range of rated currents from 16A to 100A. With adjustable tripping thresholds spanning 0.03A to 500A, it ensures faster response at higher fault levels, interrupting within 0.04 seconds at five times the rated residual current. The breaker is endurance tested for 2000 operational cycles under both load and no-load conditions.
Housed in flame-retardant and impact-resistant plastic with IP20 protection, it performs reliably even in polluted environments. Designed for 35mm DIN rail mounting, the terminals accept conductors up to 35mm² in both lug and pin types, with specified torque values such as 3.5N·m for 25mm² wiring. Its compact modular design, measuring 45mm per pole and 90.4mm in total height, saves valuable panel space. A grey operation lever provides clear ON/OFF status indication, and the unit operates without requiring auxiliary power.
Application
|
Standard |
Confirming to IEC61008-1 |
|
Protection |
Ground fault |
|
Rated current,In |
16,25,32,40,63,80,100A |
|
Number of poles |
2(1+N),4(3+N)pole |
|
Rated sensitivity currents,I△n |
10,30,100mA |
|
Rated residual non-operating current |
0.5XI△n |
|
Rated impulse withstand voltage Uimp |
6000V |
|
Rated voltages 2pole 4pole |
240VAC 240/415VAC |
|
Residual current off-time at I△n |
≤0.1s |
|
Rated residual current making &breaking capacity,I△mA |
500A for In=16,25,32,40A 630A for In=63,80,100A |
|
Rated conditional short-circuit current,Inc |
6kA |
|
Type of trip |
Electro-magnetic release |
|
Type of terminal |
Lug type and pin type |
|
Terminal capacity |
Cables up to 35mm² |
|
Degree of protection |
IP20 |
|
Installation |
35mm DIN rail |
|
Slot size |
45mm |
Product display
Endurance
|
In |
Operating cycles On-load operating cycles Off-load operating cycles |
Operating frequency (operations/h) |
|
|
16,25,32 |
2000 |
2000 |
240 |
|
40,63,80,100 |
2000 |
1000 |
120 |
Breaking time of residual current
|
Breaking time of residual current |
||||||
|
In(A) |
IΔn(A) |
IΔn |
2IΔn |
5IΔn |
5A,10A,20A,50A, 100A,200A,500A
|
|
|
16,25,32,40,63, 80,100 |
0.01,0.03,0.1,0.3 |
0.1s |
0.08s |
0.04s |
0.04s |
Max.Breaking time |
Wiring
The suitable conductors should be used for connection,see table below for relative parameters.
|
Rated current In(A) |
Nominal cross section area of lead(mm²) |
Tightening torque(N.m) |
|
16 |
2.5 |
2.5 |
|
25 |
4 |
2.5 |
|
32 |
6 |
2.5 |
|
40 |
10 |
2.5 |
|
63 |
16 |
2.5 |
|
80 |
25 |
3.5 |
|
100 |
35 |
3.5 |
Features
1. Without auxiliary power supply,the product is designed with strong immunity and extending protection range against residual current.
2. With higher rated ultimate short circuit up to 6KA
3. High reliable operation thanks to special design terminals.
4. Even under the pollution environment,the working reliability of the product will never be changed
5. Enclosure and functional parts made from imported plastics with flame-retardant,heat-resistant,and impulse-proof properties Convenient mounting
6. More flexible and reliable operation with a handle
Overall and mounting dimensions