MID Series Residual Current Circuit Breaker(RCCB)
Product Details
Product Descriprion
The MID Series offers reliable earth fault protection in compliance with IEC 61008-1 and is available in both 2-pole and 4-pole configurations. Its electromagnetic tripping mechanism swiftly detects leakage currents and interrupts within 0.1 seconds at the rated residual current. Rated for 6kV impulse voltage withstand, the device features a red and blue handle for clear OFF status indication. Housed in flame-retardant imported plastic, it remains dependable even in polluted conditions.
With an ultimate short-circuit breaking capacity of 6kA, the series covers rated currents from 16A to 100A. Its tripping sensitivity is precisely calibrated, ensuring rapid response within 0.04 seconds at five times the rated residual current. Endurance is verified through 2000 operating cycles under load for 16–32A models and 1000 cycles for 63–100A models, along with 2000 no-load cycles for sustained reliability.
Designed for 35mm DIN rail mounting, the terminals accommodate conductors up to 35mm² and include torque guidance such as 3.5N·m for 25mm² wiring. Compact dimensions of 45mm per pole width and 90.4mm total height allow space-efficient installation. The unit operates without auxiliary power and incorporates contact position indicators and pre-dimensioned mounting holes for optimized panel integration in industrial settings.
Application
|
Standard |
Confirming to IEC61008-1 |
|
Protection |
Ground fault |
|
Rated current,In |
16,25,32,40,63,80,100A |
|
Number of poles |
2(1+N),4(3+N)pole |
|
Rated sensitivity currents,I△n |
10,30,100mA |
|
Rated residual non-operating current |
0.5XI△n |
|
Rated impulse withstand voltage Uimp |
6000V |
|
Rated voltages 2pole 4pole |
240VAC 240/415VAC |
|
Residual current off-time at I△n |
≤0.1s |
|
Rated residual current making &breaking capacity,I△mA |
500A for In=16,25,32,40A 630A for In=63,80,100A |
|
Rated conditional short-circuit current,Inc |
6kA |
|
Type of trip |
Electro-magnetic release |
|
Type of terminal |
Pin type |
|
Terminal capacity |
Cables up to 35mm² |
|
Degree of protection |
IP20 |
|
Installation |
35mm DIN rail |
|
Slot size |
45mm |
Product display
Breaking time of residual current
|
Breaking time of residual current |
||||||
|
In(A) |
IΔn(A) |
IΔn |
2IΔn |
5IΔn |
5A,10A,20A,50A, 100A,200A,500A
|
|
|
16,25,32,40,63, 80,100 |
0.01,0.03,0.1,0.3 |
0.1s |
0.08s |
0.04s |
0.04s |
Max.Breaking time |
Wiring
The suitable conductors should be used for connection,see table below for relative parameters.
|
Rated current In(A) |
Nominal cross section area of lead(mm²) |
Tightening torque(N.m) |
|
16 |
2.5 |
2.5 |
|
25 |
4 |
2.5 |
|
32 |
6 |
2.5 |
|
40 |
10 |
2.5 |
|
63 |
16 |
2.5 |
|
80 |
25 |
3.5 |
|
100 |
35 |
3.5 |
Features
1. Without auxiliary power supply,the product is designed with strong immunity and extending protection range against residual current.
2. With higher rated ultimate short circuit up to 6KA
3. High reliable operation thanks to special design terminals.
4. Even under the pollution environment,the working reliability of the product will never be changed
5. Enclosure and functional parts made from imported plastics with flame-retardant,heat-resistant,and impulse-proof properties Convenient mounting
6. More flexible and reliable operation with a handle
7. With contactor condition indicator.
Overall and mounting dimensions