MLM1 MCCB
Product Details
Product Descriprion
The MLM1 and MGM1 series are versatile Molded Case Circuit Breakers (MCCBs) engineered for superior performance in electrical distribution and motor protection. This comprehensive product line covers an extensive range, with frame sizes from 63A to 1250A and adjustable rated currents spanning 10A to 800A, available in 3-pole and 4-pole configurations.
A key feature is their protective release, which utilizes a thermal-magnetic mechanism. The inverse-time delay thermal unit handles overloads, while the magnetic unit provides instantaneous tripping for short-circuits. Specific models are calibrated for either distribution protection or motor protection, with detailed trip characteristics provided for each. The breakers boast a high rated insulation voltage of up to 800V and a formidable ultimate short-circuit breaking capacity (Icu) of up to 80kA at 415V AC, with specified values for 690V AC systems as well.
For installation and application engineering, the datasheet supplies critical data. This includes recommended conductor cross-sectional areas for each current rating, total power loss values for different models, and detailed derating factors for ambient temperature variations beyond the standard 40°C, extending to 60°C. A wide array of accessories, including shunt releases, under-voltage releases, and auxiliary contacts, enhance functionality. Compliant with IEC standards, these MCCBs are characterized by their high breaking capacity, rational design, and adaptability to various industrial environments, making them a dependable choice for complex power distribution systems.
Protection Characteristics
The thermal-magnetic release features an inverse time-delay characteristic.The magnetic-only release provides instantaneous tripping;its characteristics for distribution protection are listed in the table below.
Distribution Protection
|
Rated Current of Release,In(A) |
Thermal Trip(Ambient Temperature: Land +40°C /Marine +45°C) |
Magnetic Trip Setting (A) |
|
|
1.05 In(Cold State) No-trip time(h) |
1.30 In(Hot State) Trip time (h) |
||
|
10≤In≤63 63<In≤100 |
≤1 |
≤1 |
10In±20% |
|
≤2 |
≤2 |
||
|
100<In≤800 |
≤2 |
≤2 |
5In±20% 10In±20% |
Motor Protection
|
Rated Current of- Release,In(A) |
Thermal Trip(Ambient Temperature:Land +40°C /Marine+45°C) |
Magnetic Trip Setting(A) |
|||
|
1.0 In (Cold State) No-trip time (h) |
1.20ln (Hot State) Trip time(h) |
1.50In (Hot State) Trip time(h) |
7.2 In (Cold State) Trip time (h) |
||
|
10≤In≤250 250<ln≤800 |
≤2 |
≤2 |
≤4 min ≤8 min |
4 s<Tp≤10 s 6 s<Tp≤20s |
12ln±20% |
Note: The 100A and 125A specifications for model MLM1-250 are equipped with a 5In magnetic-only release.
Release Methods and Accessory Codes
|
Model |
MLM1-63 |
MLM1-125 |
MLM1-250 |
|||||||||||
|
Number of poles |
3 |
4 |
2 |
3 |
4 |
2 |
3 |
4 |
||||||
|
Frame size current |
63 |
125 |
250 |
|||||||||||
|
Rated current(A) |
10,16,20,25,32 40,50,63 |
10,16,20,25,32 40,50,63,80,100 |
200,225,250 |
|||||||||||
|
Rated insulation vohage(V) |
500 |
800 |
800 |
|||||||||||
|
Rated operational voltagefV) |
380/400/415 |
380/400/415/690 |
380/400/415/690 |
|||||||||||
|
Arcing distance(mm) |
≤50 |
≤50 |
≤50 |
|||||||||||
|
Breaking capacity code |
S |
H |
H |
H |
S |
H |
R |
H |
H |
S |
H |
R |
H |
|
|
Frame size rated current(A) |
63 |
63 |
63 |
100 |
100 |
100 |
100 |
100 |
250 |
250 |
250 |
250 |
250 |
|
|
Ultimate short-circuit breaking capacity Icu (kA,RMS) |
AC 380V/ 400V/415V |
15 |
35 |
35 |
50 |
25 |
SO |
65 |
50 |
50 |
25 |
50 |
65 |
50 |
|
AC690V |
一 |
一 |
一 |
8 |
3 |
8 |
10 |
8 |
8 |
5 |
8 |
10 |
8 |
|
|
Service short-circuit breaking capacity lcs (kA,RMS) |
AC 380V/ 400V/415V |
7.5 |
175 |
17.5 |
25 |
125 |
25 |
325 |
25 |
25 |
12.5 |
25 |
325 |
25 |
|
AC690V |
一 |
一 |
一 |
4 |
1.5 |
4 |
5 |
4 |
4 |
2.5 |
4 |
5 |
4 |
|
|
Fixed type |
■ |
■ |
■ |
|||||||||||
|
Rear connection |
■ |
■ |
■ |
|||||||||||
|
Plug in type |
■ |
■ |
■ |
|||||||||||
|
Shunt release |
■ |
■ |
■ |
|||||||||||
|
Under-voltage ralease |
■ |
■ |
■ |
|||||||||||
|
Auxiliary contact |
■ |
■ |
■ |
|||||||||||
|
Alarm contact |
■ |
■ |
■ |
|||||||||||
|
Model |
MGM1-400 |
MGM1-630 |
MGM1-800 |
MGM1-1250 |
|||||||||
|
Number of poles |
3 |
4 |
3 |
4 |
3 |
4 |
3 |
||||||
|
Frame size current |
400 |
630 |
800 |
1250 |
|||||||||
|
Rated current(A) |
225,250,315,350,400 |
400,500,630 |
630,700,800 |
700,800 1000,1250 |
|||||||||
|
Rated insulation vohage(V) |
800 |
800 |
500 |
500 |
|||||||||
|
Rated operational voltage(V) |
380/400/415/690 |
380/400/415/690 |
380/400/415 |
380/400/415 |
|||||||||
|
Arcing distance (mm) |
<100 |
<100 |
<100 |
<100 |
|||||||||
|
Breaking capacity code |
s |
H |
R |
S |
S |
H |
R |
S |
H |
R |
H |
H |
|
|
Frame size rated current(A) |
400 |
400 |
400 |
400 |
630 |
630 |
630 |
630 |
800 |
800 |
800 |
1250 |
|
|
Ultimate short-circuit breaking capacity Icu (kA,RMS) |
AC 380V/400V/415V |
35 |
50 |
70 |
35 |
35 |
50 |
70 |
50 |
60 |
70 |
60 |
65 |
|
AC 690V |
10 |
12 |
15 |
10 |
12 |
13 |
|
12 |
– |
– |
– |
– |
|
|
Service short-circuit breaking capacity lcs (kA,RMS) |
AC 380V/400V/415V |
17.5 |
25 |
35 |
17.5 |
17.5 |
26 |
35 |
26 |
30 |
35 |
30 |
32.5 |
|
AC 690V |
5 |
6 |
7.5 |
5 |
6 |
6.5 |
|
6 |
– |
– |
– |
– |
|
|
Fixed type |
■ |
■ |
■ |
■ |
|||||||||
|
Rear connection |
■ |
■ |
■ |
■ |
|||||||||
|
Plug in type |
■ |
■ |
■ |
■ |
|||||||||
|
Shunt release |
■ |
■ |
■ |
■ |
|||||||||
|
Under-voltage release |
■ |
■ |
■ |
■ |
|||||||||
|
Auxiliary contact |
■ |
■ |
■ |
■ |
|||||||||
|
Alarm contact |
■ |
■ |
■ |
■ |
|||||||||
Cross-Sectional Area of Connecting Conductors and Suitable Rated Currents
|
Rated Current (A) |
10 |
16,20 |
25 |
32 |
40,50 |
63 |
80 |
100 |
125 |
160 |
180,200, 225 |
250 |
315, 350 |
400 |
|
Conductor Cross- Sectional Area (mm²) |
1.5 |
2.5 |
4 |
6 |
10 |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
185 |
240 |
|
Rated Current(A) |
Cable |
Copper Busbar |
||
|
|
Cross-Sectional Area (mm²) |
Quantity |
Dimensions(mm×mm) |
Quantity |
|
500 |
150 |
2 |
30×5 |
2 |
|
630 |
185 |
2 |
40×5 |
2 |
|
700,800 |
200 |
2 |
40×5 |
2 |
Power Loss
|
Model |
Energizing Current (A) |
Total 3-Pole Power Loss (VA) |
|
|
Front/Rear Mounting |
Plug-in Type |
||
|
MLM1-63(L,M) Direct-Acting (10~25A) |
25 |
28 |
32 |
|
MLM1-125 (L,M,H) Direct-Acting(10~25A) |
25 |
40 |
45 |
|
MLM1-63(L,M) Indirect-Acting(32~63A) |
63 |
20 |
24 |
|
MLM¹-125 (L,M,H) Indirect-Acting(32~125A) |
125 |
35 |
40 |
|
MLM1-250(L,M,H) |
250 |
62 |
70 |
|
MLM1-400(L,M,H) |
400 |
115 |
125 |
|
MLM1-630(L,M,H) |
630 |
187 |
200 |
|
MLM1-800(M,H) |
800 |
262 |
- |
Derating Factors for Ambient Temperature Variation
|
Model Factor Temperature |
+40° C (Marine +50° C) |
+45° C (Marine +50° C) |
+50° C (Marine +50° C) |
+55° C (Marine +50° C) |
+60° C (Marine +50° C) |
|
Derating Factor |
Derating Factor |
Derating Factor |
Derating Factor |
Derating Factor |
|
|
MLM1-63 (L,M) |
1 In |
0.94 In |
0.88 In |
0.80 In |
0.72 In |
|
MLM1-125 (L,M,H) |
1 In |
0.95 In |
0.89 In |
0.84 In |
0.76 In |
|
MLM1-250 (L,M,H) |
1 In |
0.96 In |
0.91 In |
0.87 In |
0.82 In |
|
MLM1-400 (L,M,H) |
1 In |
0.94 In |
0.87 In |
0.81 In |
0.73 In |
|
MLM1-630 (L,M,H) |
1 In |
0.93 In |
0.88 In |
0.83 In |
0.76 In |
|
MLM1-800 (M,H) |
1 In |
0.88 In |
0.83 In |
0.79 In |
0.76 In |
Note: The above derating factors are measured at the rated frame current.