MLM1 Moulded Case Circuit Breaker(DC/PV)
MCCB

MLM1 Moulded Case Circuit Breaker(DC/PV)

The DC(PV) series PV-dedicated DC circuit breakers are designed for large-scale solar plants, operating in DC250V-1500V/63A-800A grids. They provide overload long-time delay and short-circuit instantaneous protection, complying with IEC 60947 and GB 14048 standards. With horizontal/vertical mounting options and accessories like alarm contacts/shunt trips, they meet inverter isolation requirements. Integrated arc chutes ensure high breaking capacity (up to 70kA), suitable for altitudes ≤2000m and temperatures -5℃~+50℃.

    Product Details

    Product Descriprion

    The DC(PV) series PV-dedicated DC circuit breakers are engineered for large-scale solar power plants, covering high-voltage DC applications from 250V to 1500V at 63A-800A. Dual-certified to IEC 60947 and GB 14048 standards, they integrate arc-extinguishing chambers to achieve up to 70kA short-circuit breaking capacity (3P 1500V models). These breakers deliver dual protection for inverters: overload long-time delay and short-circuit.

    Revolutionary voltage-adaptive design: Single units support full-range voltage operation from DC250V to DC1500V (e.g., 400A models). Modular accessory systems (shunt trip/alarm contacts) enable remote monitoring. Busbar direct-connect technology (40x8mm terminals for 400A+ models) reduces impedance loss, while ≤100mm arc distance ensures safety in high-density installations. With 20,000 mechanical operation cycles, these breakers guarantee long-term reliability.

    Compliant with Installation Category III and Pollution Degree 3 standards, integrated phase barriers prevent arc propagation. Customizable insulating baseplates (up to 390x200mm) optimize cabinet space utilization. Certified for 2000m altitude operation, dual connection options (16mm²-120mm² wires or busbars) meet global PV plant requirements.

    1. Overview

    DC (PV) series photovoltaic special DC circuit breaker (hereinafter referred to as the circuit breaker) is used in the DC grid circuit with rated voltage of DC250V ~ DC1500V and rated working current of 63A ~ 800A. The circuit breaker has the functions of overload long delay and short circuit instantaneous protection. It is used to distribute electric energy and protect lines and power supply equipment from overload, short circuit and other fault hazards.

    This circuit breaker complies with the following standards:

    IEC 60947-1 IEC 60947-2

    GB14048.1 Low-voltage Switchgear and Control gear Part 1: General

    GB14048.2 Low-voltage Switchgear and Control gear-Part 2: Circuit Breakers

    2. Normal operating conditions

    2.1. The altitude of the installation site shall not exceed 2000 m;

    2.2. The allowable ambient temperature is not higher than + 50 ℃ and not lower than -5 ℃; (for the use of capacity reduction over + 40 ℃, the manufacturer shall be consulted for details).

    2.3 Atmospheric conditions: When the ambient temperature is 40 ℃, the relative humidity of the atmosphere shall not exceed 50%, and a higher relative humidity is allowed at a lower temperature, such as 90% at 20 ℃, and the condensation on the surface of the product due to temperature changes shall be taken into account;

    2.4 The pollution grade is Grade 3;

    2.5 The installation category is III;

    2.6. The magnetic field at the installation position shall not exceed 5 times of the geomagnetic field in any direction;

    2.7 In the medium without explosion hazard, and there is no gas and conductive dust in the medium that can corrode metal and damage insulation;

    2.8 Where there is no wind or snow erosion;

    2.9 Installation conditions:
    A) Can be installed horizontally and vertically;
    B) The installation place shall be free of obvious impact and vibration, and shall not be installed in flammable and explosive places.

    3. Mode explanation

    MLM1DC-250A3-5

    1- Enterprise Code;

    2- Plastic-enclosed circuit breaker;

    3-Design serial number;

    4- PV: PV specific; DC-dc dedicated;

    5- Shell frame grade;

    6- Operation mode: None - Direct operation;
    Z- Rotating handle operation;
    P- Electric mechanism operation

    7- Pole number

    8- Attachment Code (see the table below for details);

    9- Rated current

    10- Working voltage

    4. Main Technical Parameters

    Model

    DC、PV

    Frame rating

    250

    315

    400

    400V

    Rated current(A)

    In

    63A,80A, 100A,125A, 140A,160A, 180A,200A, 225A, 250A

    280A,

    300A,

    315A

    250A, 315A, 350A, 400A

    250A, 280A, 315A, 320A, 350A, 400A

    Rated Insulation Voltage (V)

    Ui

    1500A

    Rated Impulse Withstand Voltage (kV)​

    Uimp

    12kV

    Type

    DC

    PV

    DC

    PV

    DC

    Rated Operated Voltage((V)

    Ue

    2-Pole Config.

    DC1000V

    DC250V,DC500V,

    DC750V,DC1000V

    DC250V,DC500V,

    DC750V,DC1000V

    DC250V,DC500V,

    DC750V,DC1000V,

    DC1250V,DC1500V

    3-Pole Config.

    DC1500V

    DC1000V,DC1250V,

    DC1500V

    DC1000V,DC1500V

    ------

    Rated Ultimate Short-Circuit Breaking Capacity (kA)​

    Icu

    2-Pole Config.

    DC1000V:15

    DC250V,DC500V:50

    DC750V,DC1000V:25

    DC250V,DC500V:50

    DC750V,DC1000V:25

    DC250V,DC500V:50

    DC750V,DC1000V:25

    DC250V,DC500V:70

    DC750V,DC1000V:50

    DC1250V,DC1500V:20

    3-Pole Config.

    DC1500V:20

    DC1000V:25

    DC1250V:25

    DC1500V:25

    DC1000V:30

    DC1500V:25

    DC1000V:25

    DC1500V:25

    ---------

    Rated Service Short-Circuit Breaking Capacity (kA)​

    Ics

    100%Icu

    Wiring Method

    2-Pole Form (Fig.1), 3-Pole Form (Fig.2)

    2-Pole Form (Fig.1), 3-Pole Form (Fig.3)

    2-Pole Form (Fig.1)

    Isolation Function

    Yes

    Utilization Category

    Cat.

    A

    Mechanical Life

    cycles

    20000

    15000

    Electrical Life

    cycles

    1500

    1000

    800

    500

    Arc Distance

    mm

    >50

    >100

    Overall Dimensions

    mm

    2-Pole Config.

    200×73×135

    270×130×158

    275×106×178

    3-Pole Config.

    200×107×135

    270×182×158

    Reference Ambient Temperature

    40

    40

    Model

    DC、PV

    Frame rating

    630A

    630A

    800A

    Rated current(A)

    In

    400A, 500A, 630A

    450A,500A,630A

    630A,700A,800A

    Rated Insulation Voltage (V)

    Ui

    1500V

    Rated Impulse Withstand Voltage (kV)​

    Uimp

    12kV

    Type

    DC

    PV

    DC

    DC

    PV

    Rated Operated Voltage((V)

    Ue

    2-Pole Config.

    DC250V,DC500V,DC750V,

    DC1000V

    DC250V,DC500V,DC750V,

    DC1000V,DC1250V,DC1500V

    DC250V,DC500V,DC750V,

    DC1000V

    3-Pole Config.

    DC1000V,DC1500V

    -------

    DC1000V,DC1500V

    Rated Ultimate Short-Circuit Breaking Capacity (kA)​

    Icu

    2-Pole Config.

    DC250V,DC500V:25

    DC750V,

    DC1000V:15

    DC250V,DC500V:50

    DC750V,

    DC1000V:25

    DC250V,DC500V:70

    DC750V,DC1000V:50

    DC1250V,DC1500V:20

    DC250V,DC500V:25

    DC750V,

    DC1000V:15

    DC250V,DC500V:50

    DC750V,

    DC1000V:25

    3-Pole Config.

    DC1000V:30

    DC1500V:25

    DC1000V:40

    DC1500V:30

    -------

    DC1000V:30

    DC1500V:25

    DC1000V:40

    DC1500V:30

    Rated Service Short-Circuit Breaking Capacity (kA)​

    Ics

    100%Icu

    Wiring Method

    2-Pole Form (Fig.1), 3-Pole Form (Fig.2)

    2-Pole Form (Fig.1)

    2-Pole Form (Fig.1), 3-Pole Form (Fig.3)

    Isolation Function

    Yes

    Utilization Category

    Cat.

    A

    Mechanical Life

    cycles

    20000

    15000

    Electrical Life

    cycles

    1500

    800

    500

    Arc Distance

    mm

    >100

    >100

    Overall Dimensions

    mm

    2-Pole Config.

    270×130×158

    275×106×178

    270×130×158

    3-Pole Config.

    270×182×158

    270×182×158

    Reference Ambient Temperature

    40

    40

    Product display

    MLM1 Moulded Case Circuit Breaker(DCPV) (2)
    MLM1 Moulded Case Circuit Breaker(DCPV) (3)
    MLM1 Moulded Case Circuit Breaker(DCPV) (4)

    5. Connecting Conductor Cross-Sectional Area

    Rated current(A)

    63

    80

    100

    125/140

    160

    180/200/225

    250

    280/300/315

    350/400

    500/630

    700/800

    Conductor Cross-Sectional Area(mm²)

    16

    25

    35

    50

    70

    95

    120

    Copper busbar

    20× ×2

    Copper busbar

    30×5

    Copper busbar

    40×8

    Copper busbar

    40×5×2