Understanding the Core Differences
Surge Protective Devices (SPDs) are critical for safeguarding electrical systems against voltage spikes. However, applying the wrong type can be catastrophic.
1. Arc Extinguishing Behavior
When an SPD diverts a surge, it creates an electric arc. AC crosses zero 100 times per second (at 50 Hz), which helps naturally extinguish the arc. DC, however, flows continuously without zero-crossings. This makes DC arcs much harder to extinguish and highly prone to reignition. Therefore, DC SPDs must use specialized magnetic blow-out mechanisms to stretch and cool the arc.
2. Polarity and Voltage Ratings
AC voltage alternates polarity, whereas DC maintains a constant positive and negative. Consequently, DC SPD components must have higher dielectric strength.
- AC SPDs use Uc (Maximum Continuous Operating Voltage). Common values are 275 V, 320 V, 385 V, or 440 V AC.
- DC SPDs use Ucpv (Maximum Continuous Operating Voltage for Photovoltaics). Values typically range from 500 V up to 1500 V DC, depending on the solar string configuration.
3. Environmental Applications
AC SPDs are generally installed in standard Distribution Boards, HVAC systems, and at the AC output of inverters. DC SPDs are mandatory for photovoltaic (PV) arrays, battery energy storage systems (BESS), and EV charging stations.

Installation Best Practices & Common Mistakes
Proper installation is just as important as selecting the right SPD. Follow these guidelines to ensure system safety:
- Install as Close to the Incoming Terminals as Possible
The SPD must be wired directly across the incoming power lines. The shorter the lead length, the lower the induced voltage, ensuring the surge protector works effectively. - Use the Correct Cross-Sectional Wire
Always follow the manufacturer's datasheet for wire gauge. Wires that are too thin will overheat during a surge event. Typically, 4–6 mm² copper wire is recommended for Type 2 SPDs. - Ensure Proper Earthing
The SPD's protective earth (PE) connection must be robust. A high-impedance earth connection renders the SPD useless.
Common Mistakes to Avoid
- Swapping AC and DC units: As emphasized, never use an AC SPD on a DC circuit.
- Ignoring thermal protection: Always use an external fuse or breaker rated specifically for the SPD.
- Daisy-chaining: Do not share the same terminal block with other loads; wire the SPD independently.
How to Check if Your SPD is Damaged
SPDs have a finite lifespan. After absorbing several large surges, their internal varistors degrade.
- Visual Inspection: Most modern SPDs feature a visual status window. Green means normal operation, while Red indicates the module is exhausted and needs replacement.
- Multimeter Test: Measure the resistance across the SPD terminals. If it reads near zero (short circuit), the device has failed and must be replaced immediately to prevent a fire hazard.
- Remote Signaling: For critical infrastructure, use SPDs equipped with remote signaling contacts to trigger alarms in your monitoring system when a failure occurs.

ELECO T2 AC/DC SPD Solutions
Our Type 2 / Class II series covers both AC and DC needs, available in Shield type (compact) and OBO type (robust) mechanical designs to fit any panel layout.
AC SPD – T2 Series
| Model | Uc (V AC) | Imax (kA) | Poles | Mechanical Type |
|---|---|---|---|---|
| ELS1-D20 | 275 / 320 / 385 / 440 | 20 | 1P, 2P, 3P, 4P, 1P+N, 3P+N | Shield / OBO |
| ELS1-C40 | 275 / 320 / 385 / 440 | 40 | same | Shield / OBO |
| ELS1-H80 | 275 / 320 / 385 / 440 | 80 | same | Shield / OBO |
| ELS1-A100 | 275 / 320 / 385 / 440 | 100 | same | OBO |
DC SPD – T2 Series
| Model | Ucpv (V DC) | Imax (kA) | Poles | Mechanical Type |
|---|---|---|---|---|
| ELS1-D20 | 500 / 600 / 800 / 1000 | 20 | 2P, 3P, 4P | Shield / OBO |
| ELS1-C40 | 500 / 600 / 800 / 1000 | 40 | 2P, 3P, 4P | Shield / OBO |
Key features across all models:
- Visual status window (green = OK, red = replace)
- Plugable module on 35 mm DIN rail
- Optional remote signaling contact
- Complies with IEC 61643‑11 (AC) and IEC 61643‑31 (DC)
FAQ
Q1: Can I use an AC SPD on the DC side of a solar inverter?
No. Unless the SPD is dual‑rated (very rare), an AC SPD will fail to interrupt DC arcs and may cause a fire. Always use a dedicated DC SPD (with Ucpv rating).
Q2: What does "Ucpv" mean on a DC SPD?
It stands for "maximum continuous operating voltage for photovoltaic". It must be equal to or greater than the maximum open‑circuit voltage of your PV strings (including cold‑temperature rise).
Q3: Do I need both AC and DC SPDs in a solar system?
Yes. DC SPD protects the PV array and inverter DC input; the AC SPD protects the inverter AC output and the building's Distribution Board.
Q4: How often should I check the SPD status?
We recommend a visual inspection every 3 months. If the window turns red, replace the module immediately. For critical installations, use the remote signaling contact to monitor continuously.
Conclusion & Call to Action
Choosing the correct SPD type is essential for safety and reliability. Use AC SPD for AC circuits, DC SPD for DC circuits. In solar PV systems, both are required at different positions.
ELECO offers a full range of Type 2 AC and DC SPDs with flexible mechanical options (Shield / OBO) to suit any panel layout.
Take the next step:
- 🔍 Browse AC SPD Models– View our Type 2 AC series for Distribution Boards
- ☀️ Browse DC SPD Models – Find the right DC SPD for solar PV and BESS
- 💬 Talk to a Technical Engineer – Get personalized recommendations for your system voltage and configuration